PNACHO-O
PNACHO-O oil transformer 2000 kVA 10/0.8 kV PV Tier 2
- Rated power
- 2000 kVA
- High voltage
- 10 kV
- Low voltage
- 0.8 kV
- Rated power: 2000 kVA
- High voltage: 10 kV
- Low voltage: 0.8 kV
- Vector group: Dyn11
- No-load losses P0: ≤ 1305 W
- Load losses Pk (75 °C): ≤ 15000 W
- Short-circuit impedance uk: 6 %
- Efficiency class: Tier 2 – (EU) 2019/1783
- Standards: IEC/EN 60076, EN 50588-1
Warranty: 60 months from delivery.
Certifications: CE marking, ISO 9001, ISO 14001
PNACHO-O 2000 – 2000 kVA 10/0.8 kV
The PNACHO-O 2000 is a three-phase, hermetically sealed oil-immersed distribution transformer for 10 kV medium-voltage networks. It is engineered to European standards and complies with Ecodesign Tier 2 – Regulation (EU) 2019/1783 – for guaranteed low no-load and load losses over a service life of more than 30 years. The corrugated-wall tank without conservator requires no oil maintenance and is suitable for indoor and outdoor installation.
PV version: the 0.8 kV low-voltage winding is matched to central photovoltaic inverters (PV step-up transformer).
Technical data
| Rated power | 2000 kVA |
| High voltage | 10 kV |
| Low voltage | 0.8 kV |
| Vector group | Dyn11 |
| Tapping range | ±3 × 2.5 % (7 positions), off-circuit |
| Frequency | 50 Hz |
| Cooling | ONAN |
| No-load losses P0 | ≤ 1305 W |
| Load losses Pk (75 °C) | ≤ 15000 W |
| Short-circuit impedance uk | 6 % |
| Insulation level HV (LI/AC) | LI 75 / AC 28 kV |
| Dimensions L × W × H | 2000 × 1200 × 2150 mm |
| Total mass | ≈ 4450 kg |
| Windings | Aluminium (copper on request) |
| Protection / finish | IP00, outdoor, RAL 7033 C3 |
| Standards | IEC/EN 60076, EN 50588-1, EN 50708, (EU) 2019/1783, CE (LVD, EMC, RoHS) |
| Efficiency class | Ecodesign Tier 2 – (EU) 2019/1783 |
| Warranty | 60 months |
Standard equipment
- Hermetically sealed corrugated tank, no conservator
- Off-circuit tap changer, 7 positions (±3 × 2.5 %)
- 3 HV porcelain bushings (plug-in EUROMOLD on request), 4 LV bushings with flag terminals
- Oil level indicator, filling plug, drain valve, thermometer pocket
- Pressure relief device
- Bi-directional rollers, 2 lifting lugs, earthing terminals
- Rating plate and wiring diagram
- Mineral oil to IEC 60296 (ester MIDEL 7131 on request)
- Protection relay DGPT2 / DMCR
Testing and conformity
Every unit undergoes routine tests to IEC 60076: no-load loss and current, load loss and impedance at 75 °C, winding resistance, voltage ratio and vector group, induced and applied voltage withstand, insulation resistance, tank tightness test (30 kPa / 12 h). Type tests (lightning impulse, temperature rise, short-circuit withstand, sound level) are available on request. Each transformer is delivered with test report, EU declaration of conformity (CE – LVD, EMC, RoHS, Ecodesign) and operating manual.
Applications
Photovoltaic and battery storage plants, wind farms, hybrid renewable installations.
Delivery and warranty
Made to order, delivery in 16 weeks; other voltage ratios, vector groups, copper windings and accessories on request. 5-year warranty. Delivery to any EU country, technical support in English, German and Polish.
Optional equipment
- Copper windings (Cu/Cu)
- DGPT2 / DMCR protection relay
- Plug-in EUROMOLD HV bushings 250 A / 24 kV
- Ester oil MIDEL 7131 (K-class, increased fire safety)
- Low-voltage 0.4 kV or 0.69 kV
- Vector group Dyn5 or Yzn5
- Anti-vibration pads, bird-protection covers
- On-load tap changer (from 1000 kVA)
- Enclosure IP23 / IP33
Our offer is for businesses only. All prices are net, plus VAT.