PNACHO-D
PNACHO-D dry transformer 250 kVA 10/0.42 kV Tier 2
- Rated power
- 250 kVA
- High voltage
- 10 kV
- Low voltage
- 0.42 kV
- Rated power: 250 kVA
- High voltage: 10 kV
- Low voltage: 0.42 kV
- Vector group: Dyn11
- No-load losses P0: ≤ 468 W
- Load losses Pk (120 °C): ≤ 3400 W
- Short-circuit impedance uk: 6 %
- Efficiency class: Tier 2 – (EU) 2019/1783
- Standards: IEC/EN 60076-11, EN 50588-1
Warranty: 60 months from delivery.
Certifications: CE marking, ISO 9001, ISO 14001
PNACHO-D 250 – 250 kVA 10/0.42 kV
The PNACHO-D 250 is a three-phase, vacuum-cast epoxy-resin dry-type transformer for 10 kV networks in buildings and industrial plants where fire safety matters: self-extinguishing class F1, climatic class C3 and environmental class E3 to IEC/EN 60076-11. It complies with Ecodesign Tier 2 – Regulation (EU) 2019/1783 – and needs no oil, no bund and no fire-suppression system.
Technical data
| Rated power | 250 kVA |
| High voltage | 10 kV |
| Low voltage | 0.42 kV |
| Vector group | Dyn11 |
| Tapping range | ±2 × 2.5 % (5 positions), off-circuit |
| Frequency | 50 Hz |
| Cooling | AN (AF +40 % on request) |
| No-load losses P0 | ≤ 468 W |
| Load losses Pk (120 °C) | ≤ 3400 W |
| Short-circuit impedance uk | 6 % |
| Sound level | 43 dB(A) |
| Insulation level HV (LI/AC) | LI 75 / AC 28 kV |
| Dimensions L × W × H | 1270 × 750 × 1380 mm |
| Total mass | ≈ 1070 kg |
| Windings | Aluminium, vacuum-cast epoxy (copper on request) |
| Protection / finish | IP00 indoor (IP21–IP44 enclosure on request), class C3/E3/F1, insulation class F |
| Standards | IEC/EN 60076-11, EN 50588-1, EN 50708, (EU) 2019/1783, CE (LVD, EMC, RoHS) |
| Efficiency class | Ecodesign Tier 2 – (EU) 2019/1783 |
| Warranty | 60 months |
Standard equipment
- Vacuum-cast epoxy HV windings, aluminium foil LV windings
- Grain-oriented, step-lap core with anti-corrosion coating
- Off-circuit tapping links ±2 × 2.5 %
- 3 × PT100 sensors in LV windings + temperature monitoring relay T-154
- Bi-directional rollers, lifting lugs, earthing terminals
- Rating plate and wiring diagram
- Partial discharge ≤ 10 pC
Testing and conformity
Every unit undergoes routine tests to IEC 60076: no-load loss and current, load loss and impedance at 120 °C, winding resistance, voltage ratio and vector group, induced and applied voltage withstand, insulation resistance. Type tests (lightning impulse, temperature rise, short-circuit withstand, sound level) are available on request. Each transformer is delivered with test report, EU declaration of conformity (CE – LVD, EMC, RoHS, Ecodesign) and operating manual.
Applications
Hospitals, data centres, shopping centres, high-rise and public buildings, tunnels and underground installations, industrial halls, indoor substations.
Delivery and warranty
Made to order, delivery in 16 weeks; other voltage ratios, vector groups, copper windings and accessories on request. 5-year warranty. Delivery to any EU country, technical support in English, German and Polish.
Optional equipment
- Copper windings (Cu/Cu)
- Enclosure IP21 – IP44
- Forced-air cooling AF (+40 % power)
- Low-voltage 0.4 kV or 0.69 kV
- Vector group Dyn5
- Dual-voltage HV winding (e.g. 10/21 kV)
- Anti-vibration pads, surge arresters
- Enclosure temperature sensors and fan control
Our offer is for businesses only. All prices are net, plus VAT.