PNACHO-D 2000 – 2000 kVA 10/0.42 kV Cast-Resin Dry-Type Transformer

PNACHO-D

PNACHO-D dry transformer 2000 kVA 10/0.42 kV Tier 2

Rated power
2000 kVA
High voltage
10 kV
Low voltage
0.42 kV
  • Rated power: 2000 kVA
  • High voltage: 10 kV
  • Low voltage: 0.42 kV
  • Vector group: Dyn11
  • No-load losses P0: ≤ 2340 W
  • Load losses Pk (120 °C): ≤ 16000 W
  • Short-circuit impedance uk: 6 %
  • Efficiency class: Tier 2 – (EU) 2019/1783
  • Standards: IEC/EN 60076-11, EN 50588-1

Warranty: 60 months from delivery.

Certifications: CE marking, ISO 9001, ISO 14001

PNACHO-D 2000 – 2000 kVA 10/0.42 kV

The PNACHO-D 2000 is a three-phase, vacuum-cast epoxy-resin dry-type transformer for 10 kV networks in buildings and industrial plants where fire safety matters: self-extinguishing class F1, climatic class C3 and environmental class E3 to IEC/EN 60076-11. It complies with Ecodesign Tier 2 – Regulation (EU) 2019/1783 – and needs no oil, no bund and no fire-suppression system.

Technical data

Rated power2000 kVA
High voltage10 kV
Low voltage0.42 kV
Vector groupDyn11
Tapping range±2 × 2.5 % (5 positions), off-circuit
Frequency50 Hz
CoolingAN (AF +40 % on request)
No-load losses P0≤ 2340 W
Load losses Pk (120 °C)≤ 16000 W
Short-circuit impedance uk6 %
Sound level55 dB(A)
Insulation level HV (LI/AC)LI 75 / AC 28 kV
Dimensions L × W × H1785 × 1310 × 2260 mm
Total mass≈ 4310 kg
WindingsAluminium, vacuum-cast epoxy (copper on request)
Protection / finishIP00 indoor (IP21–IP44 enclosure on request), class C3/E3/F1, insulation class F
StandardsIEC/EN 60076-11, EN 50588-1, EN 50708, (EU) 2019/1783, CE (LVD, EMC, RoHS)
Efficiency classEcodesign Tier 2 – (EU) 2019/1783
Warranty60 months

Standard equipment

  • Vacuum-cast epoxy HV windings, aluminium foil LV windings
  • Grain-oriented, step-lap core with anti-corrosion coating
  • Off-circuit tapping links ±2 × 2.5 %
  • 3 × PT100 sensors in LV windings + temperature monitoring relay T-154
  • Bi-directional rollers, lifting lugs, earthing terminals
  • Rating plate and wiring diagram
  • Partial discharge ≤ 10 pC

Testing and conformity

Every unit undergoes routine tests to IEC 60076: no-load loss and current, load loss and impedance at 120 °C, winding resistance, voltage ratio and vector group, induced and applied voltage withstand, insulation resistance. Type tests (lightning impulse, temperature rise, short-circuit withstand, sound level) are available on request. Each transformer is delivered with test report, EU declaration of conformity (CE – LVD, EMC, RoHS, Ecodesign) and operating manual.

Applications

Hospitals, data centres, shopping centres, high-rise and public buildings, tunnels and underground installations, industrial halls, indoor substations.

Delivery and warranty

Made to order, delivery in 16 weeks; other voltage ratios, vector groups, copper windings and accessories on request. 5-year warranty. Delivery to any EU country, technical support in English, German and Polish.

Optional equipment

  • Copper windings (Cu/Cu)
  • Enclosure IP21 – IP44
  • Forced-air cooling AF (+40 % power)
  • Low-voltage 0.4 kV or 0.69 kV
  • Vector group Dyn5
  • Dual-voltage HV winding (e.g. 10/21 kV)
  • Anti-vibration pads, surge arresters
  • Enclosure temperature sensors and fan control

Our offer is for businesses only. All prices are net, plus VAT.